Dynamic modeling and control implementation of a chiller unit

Télécharger
Heremans, Sophie ULiège
Promoteur(s) : Lemort, Vincent ULiège
Date de soutenance : 27-jui-2016/28-jui-2016 • URL permanente : http://hdl.handle.net/2268.2/1391
Détails
Titre : Dynamic modeling and control implementation of a chiller unit
Auteur : Heremans, Sophie ULiège
Date de soutenance  : 27-jui-2016/28-jui-2016
Promoteur(s) : Lemort, Vincent ULiège
Membre(s) du jury : Dechesne, Bertrand ULiège
Quoilin, Sylvain ULiège
Bertagnolio, Stéphane 
Langue : Anglais
Nombre de pages : 105
Mots-clés : [fr] Dymola, Chiller, Modeling, Dynamic
Discipline(s) : Ingénierie, informatique & technologie > Energie
Organisme(s) subsidiant(s) : Emerson Climate Technologies
Public cible : Autre
Institution(s) : Université de Liège, Liège, Belgique
Diplôme : Master en ingénieur civil électromécanicien, à finalité approfondie
Faculté : Mémoires de la Faculté des Sciences appliquées

Résumé

[en] The aim of this master thesis is to implement a model that will simulate the dynamic behavior of an air-to-water chiller unit in the further with a view of running Hardware-in-the-loop simulations to test hardware control unit. First the calibration and steady state modeling of the chiller components are conducted in EES Software. The calibration is based on steady state experimental data in order to tune components parameters. Then the dynamic model of each component is implemented in Dymola Software. In Dymola, the model of the plate heat evaporator as well as the fin and tubes condenser are based on the finite-control volume method. The scroll compressors are modeled with regression laws based on empirical polynomial equations developed by Emerson. A new mass flow correlation for the EEV is developed especially for the purpose of this study. The equations modeling the fan are obtained by similitudes analysis and involve Rateau's dimensionless coefficients. Finally pressure drops due to piping are determined thanks to experimental data. After validation of each model with experimental data, the components were assembled. To test the modeled unit and observe its behavior during transients a controller is developed. This simple control unit manages the evaporator superheat, the fan, the speed of the variable speed compressor and the fixed speed compressor. A simulation is run to validate the model and to ensure that its behavior matches the one of the real unit under transients. Finally several superheat control strategies are simulated to characterize the benefit on the compressors power consumption.


Fichier(s)

Document(s)

File
Access TFE_S112707.pdf
Description:
Taille: 12.44 MB
Format: Adobe PDF
File
Access Erratum_TFE_S112707.pdf
Description: -
Taille: 96.77 kB
Format: Adobe PDF

Annexe(s)

File
Access abstract.pdf
Description:
Taille: 62.95 kB
Format: Adobe PDF

Auteur

  • Heremans, Sophie ULiège Université de Liège > Master ing. civil électro., fin. appr. (ex 2e master)

Promoteur(s)

Membre(s) du jury

  • Dechesne, Bertrand ULiège Université de Liège - ULg > Département d'aérospatiale et mécanique > Systèmes énergétiques
    ORBi Voir ses publications sur ORBi
  • Quoilin, Sylvain ULiège Université de Liège - ULg > Département d'aérospatiale et mécanique > Systèmes énergétiques
    ORBi Voir ses publications sur ORBi
  • Bertagnolio, Stéphane Emerson Climate Technologies GmbH, rue des Trois Bourdons, 27, 4840 Welkenraedt
  • Nombre total de vues 53
  • Nombre total de téléchargements 0










Tous les documents disponibles sur MatheO sont protégés par le droit d'auteur et soumis aux règles habituelles de bon usage.
L'Université de Liège ne garantit pas la qualité scientifique de ces travaux d'étudiants ni l'exactitude de l'ensemble des informations qu'ils contiennent.